Well Water Treatment System: Match Test Results to a Fix

Choose a well water treatment system from your lab report: thresholds and the right technology for 11 common problems, plus installer and upkeep tips.

Pick a well water treatment system from your lab report, not from a product page. Find each result that exceeds its threshold, match it to the technology in the table below, and fix the source first if you can, such as a cracked well cap or a nearby septic line. MDH notes that no single unit removes everything, so a well with several problems needs several stages. The whole house water filter hub shows the order to plumb them in.

If you don’t have a recent lab report, start with well water testing. UGA Extension recommends testing bacteria and nitrate every year.

Problem → treatment matrix

Test resultThreshold (source)Treatment technologyPOE or POURead more
Total coliform / E. coliShould be absent (UGA B 939)Shock chlorination, then continuous chlorination or NSF 55 Class A UV if it returnsPOEColiform, UV
Nitrate10 mg/L as nitrogen (EPA MCL)Reverse osmosis or distillation for drinking water; anion exchange for the whole housePOU (RO), POE (anion)Nitrates, RO
Arsenic10 µg/L (EPA MCL; MDH action level)Adsorptive media (iron or titanium based), RO, anion exchange, oxidation filtrationPOE or POURO
Iron / manganese0.3 mg/L Fe, 0.05 mg/L Mn (EPA secondary)Softener (low dissolved iron), greensand or other oxidizing filter, chlorination plus filtration at high levelsPOEIron hub, Iron removal
Hydrogen sulfideMost people smell it well below 0.5 mg/L (Penn State)Carbon below about 1 mg/L; greensand up to about 2–3 mg/L; chlorination or permanganate above 6 mg/LPOESulfur smell
Low pHBelow 6.5 (EPA secondary range 6.5–8.5)Calcite or magnesium oxide neutralizer; soda ash feed pumpPOEAcid neutralizers
HardnessAbout 7 gpg (about 120 mg/L) interferes with soap (UGA)Cation-exchange softenerPOEWater softeners
Sediment / turbidityAbove 5 NTU suggests possible bacteria (UGA); above 1 NTU needs pretreatment before UV (UConn)Cartridge or backwashing sand filterPOESediment filters
TanninsYellow-brown color (no EPA health standard)Anion exchange above pH 6; activated carbon below pH 5 (WQA)POEFiltration systems
RadonNo federal standard (EPA); consider action above 4,000 pCi/L (Wisconsin DNR)Aeration; granular activated carbonPOE onlyFiltration systems
PFAS (PFOA, PFOS)4.0 ng/L each (EPA MCL for public systems)Granular activated carbon, RO, ion exchange certified to NSF/ANSI 53 or 58POU or POERO

Notes the table can’t hold

Bacteria

UGA recommends finding and removing the contamination source first: surface water at the casing, a septic line too close to the well, or livestock runoff. Then shock chlorinate. Use continuous disinfection only if coliform comes back. Colorado State Extension notes that chlorination leaves a residual in the plumbing and UV does not. UGA advises against UV when untreated water exceeds 1,000 total coliform or 100 fecal coliform per 100 mL.

Nitrate and arsenic

Neither one responds to boiling. MDH warns that boiling concentrates both. A conventional softener doesn’t remove nitrate or arsenic, and MDH adds that carbon alone won’t remove arsenic either. MDH also recommends that babies under 6 months not drink the well water even after nitrate treatment. UGA notes that some RO units are certified only for arsenic V and not arsenic III, so check the certification listing for the form your lab reported. UGA also warns that anion exchange can leave water corrosive, so it may need a neutralizer after it.

Iron, manganese and hydrogen sulfide

Penn State’s limits:

  • Softener: dissolved iron below 5 mg/L, at pH above 6.7 and hardness of 3 to 20 gpg.
  • Greensand: about 3 to 10 mg/L of combined iron and manganese.
  • Above 10 mg/L combined: oxidation followed by filtration.

If the rotten-egg smell shows up only in hot water, Penn State points to the water heater’s magnesium anode, which an aluminum rod usually fixes without any treatment equipment.

Low pH

Virginia Tech Extension notes that neutralizer media dissolves into the water and adds hardness, so a softener may be needed after it. UGA lists soda ash feed as the alternative. UGA notes it can share a feed pump with chlorine when disinfection is also needed.

Radon and PFAS

Wisconsin DNR calls aeration the most effective radon treatment. It describes GAC as effective, but spent carbon from water at 4,000 pCi/L or higher can hold hazardous radiation levels. Small faucet or under-sink filters are inadequate for radon. UGA notes that RO doesn’t remove dissolved gases, radon included. For PFAS, EPA says certifications currently focus on PFOA and PFOS, and filters only work when they’re replaced on the manufacturer’s schedule.

How to pick an installer

  1. Check the license. Minnesota requires a licensed plumbing or water conditioning contractor for installs. Other states differ, so ask your county health department.
  2. Verify certification. MDH points buyers to units certified by NSF, UL or WQA for the specific contaminant. Look the model up in the certifier’s listing yourself. UGA warns that “tested to NSF standards” wording is not proof of certification.
  3. Get two quotes. UGA advises comparing at least two dealers and brands, checking references, and having a qualified person review your results before you buy. In-home tests can’t measure arsenic, uranium or organics.
  4. Put the follow-up test in writing. UGA recommends a written guarantee tied to a water test about 1 to 2 months after installation.
  5. Ask about total cost. That means installation, salt and media, electricity, cartridges, RO reject water, and whether doing your own maintenance voids the warranty.
  6. Check the plumbing details. Minnesota’s rule requires isolation and bypass valves on every water conditioning install and an air gap where backwash water enters the drain.

Maintenance schedule

TaskIntervalSource
Test treated water for bacteria and nitrateEvery yearUGA B 939; MDH
Follow-up test after a new installAbout 1–2 months afterUGA B 939
Replace the UV lampEvery 9–12 monthsColorado State
Test water after UV for bacteriaPeriodically, to verify performanceUGA B 939
Replace the sediment cartridgeWhen clogged; don’t leave a spent cartridge in placeUGA B 939
Replace the carbon media or cartridgeAt the manufacturer’s capacity; spent carbon can grow bacteriaUGA B 939; UConn
Regenerate greensand with potassium permanganateWhen oxidizing capacity dropsPenn State; UGA B 939
Backwash and top up neutralizer mediaAs the bed dissolves; the rate depends on pH and water useVirginia Tech; UGA B 939
Mix fresh chlorine stock solutionAt least weeklyUGA B 939
Replace the RO membrane and prefiltersOn the manufacturer’s schedule; test before and after ROUGA B 939
Fill the softener brine tank with saltAs the manufacturer directsUGA B 939

MDH warns that units that aren’t maintained lose effectiveness and can make water quality worse. Write the intervals on the equipment and add a reminder to your calendar.

Choosing the hardware

Once you know which stages you need, compare packaged well water filtration systems. Add UV for bacteria, a sediment filter ahead of everything, and reverse osmosis at the kitchen tap for nitrate, arsenic or PFAS.

Sources

  1. EPA — National Primary Drinking Water Regulations
    arsenic 0.010 mg/L; nitrate 10 mg/L as N; PFOA and PFOS 4.0 ng/L (public systems)
  2. EPA — Secondary Drinking Water Standards
    iron 0.3 mg/L; manganese 0.05 mg/L; pH 6.5–8.5
  3. University of Georgia Extension — Water Quality and Common Treatments for Private Drinking Water Systems (B 939)
    coliform absent; UV limits of 1,000 total / 100 fecal coliform per 100 mL; arsenic media; nitrate options; hardness 7 gpg; turbidity 5 NTU; dealer checklist; maintenance; test intervals
  4. Minnesota Department of Health — Arsenic in Well Water
    act above 10 µg/L; softeners and carbon alone don't remove arsenic; licensed installer
  5. Minnesota Department of Health — Nitrate in Well Water
    don't boil; test yearly; infants under 6 months
  6. Minnesota Department of Health — Home Water Treatment
    certification by NSF, UL or WQA; licensed plumber or water conditioning contractor; test after install
  7. Minnesota Rules 4714.0611 — Water conditioning equipment
    isolation and bypass valves; air-gap discharge; NSF/ANSI 61 materials
  8. Penn State Extension — Iron and Manganese in Private Water Systems
    technology by mg/L of iron and manganese
  9. Penn State Extension — Hydrogen Sulfide (Rotten Egg Odor) in Water Wells
    odor below 0.5 mg/L; technology by mg/L band; anode rod
  10. Colorado State University Extension — Bacteria in Water Wells
    UV has no residual; UV lamp every 9–12 months
  11. UConn Extension — Managing Your Private Well, Water Treatment Guide
    UV pretreatment above 1 NTU; carbon and RO for PFAS
  12. Water Quality Association — Glossary of Terms (Tannin)
    anion exchange above pH 6; activated carbon below pH 5
  13. Wisconsin DNR — Radon in Private Well Water
    consider action above 4,000 pCi/L; aeration and GAC; POU filters inadequate
  14. EPA (archive) — Radon in Drinking Water Questions and Answers
    no federally enforced radon standard
  15. EPA — PFAS in Private Wells
    GAC, RO, ion exchange; NSF/ANSI 53 or 58
  16. Virginia Tech Extension — Household Water Treatment (442-670)
    neutralizers add hardness; media replenishment